The VVK 1(2)-10-20/630 (1000) U3 vacuum circuit breakers are three-phase electric devices with electromagnetic drive and mechanical gate ensuring reliable fixation of the device while it is operational. Such vacuum circuit breakers are designated for commutation of electric circuits under normal as well as emergency operation modes in three-phase alternating current networks of 50 GHz frequency and 10 KV voltage. They are supposed for installation within dispatching control units and monitoring/signaling units, including the possibility of replacing the oil circuit breakers. The devices are equipped with the vacuum arc chutes of our own manufacture. The control circuit of the electromagnetic drive of these vacuum circuit breakers is located within the housing of the device and is easy to use. The design of the lithium caps made of a firm material of Lexan-type ensures reliable protection of the vacuum chambers against the environmental impacts.

Technical properties
Main technical properties Permissible values
Nominal voltage, KV
а10
Maximum operating voltage, KV
а12
Nominal current, A
630 (1000)
Electrical (transient) resistance of each terminal of the main circuit, micro Ohm, not exceeding
75 (60)
Nominal breaking current, KA
а20
Normalized parameters of making current, KA:
- initial actual value of periodic component
- maximum peak
а
20
а52
Normalized parameters of the short-circuit steady leakage current, KA:
- maximum peak (electrodynamics endurance current)

52
- mean-square value of the current over the time of its flowing (thermal endurance current for a period of three (3) seconds)
20
- initial actual value of periodic component
а20
Normalized abundance of unidirectional component, %, not exceeding
а40
Intrinsic turn-on time, sec, not exceeding
0,1
Intrinsic disconnection time, sec, not exceeding
0,040
Total disconnection time, sec, not exceeding
0,055
Supply voltage of control circuit (direct or alternating), V
220
Supply current of turn-on electrical magnet, A, not exceeding
а30
Supply current of turn-off electrical magnet, A, not exceeding
аа 6
Commutation resource (number of cycles):
- under nominal current
- under nominal breaking current

75000
100
Range of ambient temperatures, 0
from -40 to +55
Dimensions, mm
550 ї 216 ї 688
Weight of device, kg
72 (74)
├рЁрэЄшщэ√щ ёЁюъ ¤ъёяыєрЄрЎшш
3 year
Service life
25 year